The Modeling and Simulation in Electrical and Electronics Engineering، جلد ۴، شماره ۳، صفحات ۱-۹
|
|
|
عنوان فارسی |
|
|
چکیده فارسی مقاله |
|
|
کلیدواژههای فارسی مقاله |
|
|
عنوان انگلیسی |
An Overview of Harmonic Analysis and Filter Selection for an Industrial Plant |
|
چکیده انگلیسی مقاله |
This paper presents a harmonic analysis and the design and selection of harmonic filters for a hybrid cooling tower at a refinery plant. This study can be extended to any industrial plant with numerous variable speed drives (VSD). In this industrial complex, variable speed drives constitute the total load of power transformers. The harmonic analysis of the system shows that harmonic elimination with passive filters is possible only for certain current and power ranges. The studies also indicate that ferro-resonance occurs under light load conditions. This phenomenon creates over-voltages in the network and damages the equipment. The purpose of this paper is to highlight important points in the design or selection of voltage harmonic filters in industrial networks with large non-linear loads. |
|
کلیدواژههای انگلیسی مقاله |
Industrial plants harmonic Analysis,Industrial plants harmonic filter design,Passive harmonic filter limitations,Harmonic elimination,Harmonic rejection,Passive Filters Resonance,Passive Filters Ferro-Resonance |
|
نویسندگان مقاله |
Behnam Ahmadnezhad | Faculty of Electrical and Computer Engineering Department, Semnan University, Semnan, Iran.
Hamid Reza Izadfar | Faculty of Electrical and Computer Engineering Department, Semnan University, Semnan, Iran.
|
|
نشانی اینترنتی |
https://mseee.semnan.ac.ir/article_9476_3311cfc44c6638fa32eeeaa3cc84b2eb.pdf |
فایل مقاله |
فایلی برای مقاله ذخیره نشده است |
کد مقاله (doi) |
|
زبان مقاله منتشر شده |
en |
موضوعات مقاله منتشر شده |
|
نوع مقاله منتشر شده |
|
|
|
برگشت به:
صفحه اول پایگاه |
نسخه مرتبط |
نشریه مرتبط |
فهرست نشریات
|